| Ribbon/Toolbar (Software) | Button | Function | Error Type | Description | ||
|---|---|---|---|---|---|---|
| Ribbon/Toolbar (Software) | Button | Function | Error Type | Description | ||
| Card 157 View | 3D Modeling (AutoCAD Based) | Show System Model | None | None | blank or incomplete job path job path |
|
| Card 258 View | Hangers (AutoCAD Based) | Insert One Hanger | None | None | Hanger length attribute is missing. The hanger inserts only the assembly number even if the HIDE NUMBER box is checked in the Hanger Setup. A V45 hanger block is in the drawing. It has only one attribute value & can display only the number. HydraCAD v50 |
|
| Card 263 View | Steel (AutoCAD Based) | Structure Elevations | None | None | when placing a TOS defline and a item is picked to place the Tos defline. If the item has a Z coordinate then this can be assinged the TOS block. the defline will be a 0 but the blocks will be elevated (although it looks normal) this will usually raise once and then the error will occur even if you put a new defline in. tos id missing |
|
| Card 359 View | Build 3D Risers (AutoCAD Based) | Insert Fitting Via HydraList | None | None | Unknown NET.framework Insert interface |
|
| Card 445 View | Build 3D Risers (AutoCAD Based) | Insert Fitting Via HydraList | None | None | Bug in software. The pipe created in the MAINS tab of HydraLIST is Metric but HydraCAD believes the pipe is Imperial, therefore it scales it up by 25.4 n/a n/a Hcad v52+ |
|
| Card 353 View | Build 3D Risers (AutoCAD Based) | Insert Fitting Via HydraList | None | None | Outlets are missing from a main that has been listed in HydraLIST. The section ID has a space or other special chacter in the name. |
|
| Card 247 View | Hangers (AutoCAD Based) | Insert One Hanger | None | None | 1. HydraCAD v45 SMaRT drawing in HydraCAD v50 bad argument HydraCAD v50 |
|
| Card 401 View | HydraCALC (Standalone) | Print Final | None | None | 1. The info sheet has symbols when it is expecting a number or blank, i.e. "Rack Sprinkler Demand" is N/A instead of blank or 0. Error:Bad Argument 52.02+ |
|
| Card 146 View | Listing (AutoCAD Based) | Start Autolist | None | Runtime Error | Microsoft Jet Database engine cannot open the file ...... Runtime Error 14 |
|
| Card 522 View | 3D Modeling (AutoCAD Based) | Show System Model | None | None | It was not the 3D command that broke things, it was OVERKILL Go to 3D |
|
| Card 341 View | Calculations (AutoCAD Based) | Start Autocalcs | None | None | Unable to write files to hard drive HES folders (among others) were not 'active' in that they appeared faint yellow when looking at them in Windows Explorer/My Computer AutoCalc/Checkups |
|
| Card 255 View | Cleanup (AutoCAD Based) | Draw Pretty Pipes | None | Unhandled Exception | Bad prettypipes.dat file Bug with the new Flexible Hose Connections. Drawing with FHCs will get this error, drawings without will not get the error Unhandled Except. Dialog Box v50 |
|
| Card 164 View | Listing (AutoCAD Based) | Start Autolist | None | None | operation failed |
|
| Card 434 View | Piping (AutoCAD Based) | Schedule Sizes | None | Runtime Error | unknown n/a Run-time Error 380 n/a |
|
| Card 302 View | Piping (AutoCAD Based) | Size Pipe Setup | None | None | Cannot insert pipe diameters or cut in couplings that also insert pipe diameters. |
|
| Card 153 View | Listing (AutoCAD Based) | Start Autolist | None | Unhandled Exception | external component has thrown an exception unhandled exception |
|
| Card 524 View | Sprinklers (AutoCAD Based) | Insert Sprinkler | None | None | missing data files in \HES\HYDRACAD\Ver50\DATA\SETUP Selecting |
|
| Card 280 View | Build 3D Risers (AutoCAD Based) | Insert Fitting Via HydraList | None | None | Registry Keys not set |
|
| Card 162 View | Listing (AutoCAD Based) | Start Autolist | None | Dao Error | Process Autolist box comes up and hangs at green arrow. DAO Server error - DB Create dialog box comes up with the stocklist path and Not a Valid File Name. Autocad will close with an unhandled exception. Error DB Create |
|
| Card 446 View | Sprinklers (AutoCAD Based) | Insert Sprinkler | None | None | The BLKRDEF1 sprinkler definition block was revised to include the 3D Head Block name and Head Adjustment (drop/sprig take out) attributes. The drawing has an older BLDRDEF1 sprinkler definition block inserted before the update. HydraCAD V52 V53 |
|