Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

Revit Based HydraCALC (Ribbon/Toolbar/Location)

Button: Hydraulic Calculations Function: Return To Revit Error Type: Command Failure for External Command

Description:

Error placing Reference Points or Demand Area annotation.: System NullReferenceException: Object reference not set to an instance of an object. nodes reference finish


Solutions:

Cause:

Cannot insert demand annotation or reference points. After error "ALL REF POINTS" button from ribbon does not insert nodes.

Solution:

Error was caused by several pipes in the system with open ends. Customer capped all open pipes, ran the calculation process again and was able to complete the process. The demand annotation and reference (node) points inserted properly.

Updated: Dec. 6, 2024, 1:43 p.m. Created: Nov. 13, 2018, midnight