Ribbon/Toolbar (Software) Button Function Error Type Description
Ribbon/Toolbar (Software) Button Function Error Type Description
Card 482 View Calculations (AutoCAD Based) Start Autocalcs Pipe Schedule None

Bad Registry Entry n/a Dialog Window HydraCALC

Card 410 View Calculations (AutoCAD Based) Figure Head Area None None

Bad setting of Acad variable

drawing area 53.02 rev 2

Card 238 View Piping (AutoCAD Based) Riser Nipple Setup None None

1. Install may not have configured properly. 2. Possibly a rogue lisp routine causing ours not to work HydraCAD v50.any

Card 447 View Calculations (AutoCAD Based) Dummy Reference Points None None

The blocks FAKEREF.DWG & FAKEREF2.DWG are not being inserted to the drawing. Unknown reason because the code should do that automatically. All tests in office work fine. n/a Dialog Box 53.03

Card 375 View Piping (AutoCAD Based) Size Pipe Setup None None

Unknown 2013 V52

Card 295 View 3D Modeling (AutoCAD Based) Show System Model None None

Cannot read the HydraPipe dictionary Hydrapipes dictionary needs to be overwritten solid pipes 3d modeling v50+

Card 455 View Piping (AutoCAD Based) Edit Riser Nipples None None

Using AutoCAD's ROTATE command will not rotate a VP HydraCAD v52+

Card 167 View Listing (AutoCAD Based) Start Autolist None None

Some threaded branch lines are not being tagged automatically as expected. Automatic Line Tags are missing after running AutoLIST. none

Card 453 View 3D Modeling (AutoCAD Based) Show System Model None None

Possible bad System Boundary.

Card 246 View Piping (AutoCAD Based) Insert One RN None Runtime Error

1. Trying to insert an RN on a drawing that has not been converted to v50 2. An incorrectly edited VP from v45 has bad text Runtime error 9

Card 352 View Calculations (AutoCAD Based) Figure Head Area Dialog Box None

APQ block is not in the block table FATAL ERROR Dialog Box HydraCAD v52

Card 308 View Sprinklers (AutoCAD Based) Insert Sprinkler Head Block Definition None

Text is the wrong size due to DIMTXT setting. Possibly caused by changing annotative scales. V50/V51

Card 424 View Piping (AutoCAD Based) Riser Nipple Setup Dialog Box None

Avast Virus Checker believes the file has a virus n/a Dialog Box Acad 2015

Card 409 View Collaborate (AutoCAD Based) Revit Toolkit Create Revit link to Drawing None

1. Loading Revit content into a non-MEP template (ie Construction or Architectural template) Revit

Card 495 View Collaborate (AutoCAD Based) Revit Toolkit Create Revit link to Drawing None

1. Our Addin file is looking in the wrong location for our Revit tools Revit

Card 467 View Persistent Model (AutoCAD Based) Export None None

The lines or mains do not get the pretty pipes applied. The layer is all lower case. Lines or Mains missing

Card 163 View Listing (AutoCAD Based) Listing Check Ups None None

During checkups, the process abruptly ends and reports "Exception occurred" on the command prompt Command prompt

Card 381 View Listing (AutoCAD Based) New Tag None None

??? Error when picking NewTag button. Connection Failed listing tags

Card 449 View Calculations (AutoCAD Based) Add Calculation Fittings None None

Error occurs when "Add Calculation Fittings" is used when running AutoCALC the first time after a new install. A registry entry for one of the Pipe Schedule properties is not set in the registry. (The Pipe Schedule is connected to fittings definitions.) error 75

Card 244 View Piping (AutoCAD Based) Edit Riser Nipples None None

Insert RN , it asks for Higher\lower pipe then dissapears. Probalble bad configuration dissapear