Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

Standalone HydraCALC (Location)

Button: Print Error Type: Runtime Error

Description:

When trying to print final, the dialog box HydraVIEW, Run-time error 9, Subscript out of range

Solutions:


1.
Cause:

Most likely due to an error during the calculation process which indicated the calc process was not complete.  Common error is a Loss Curve message as indicated in this HydraCARD;

https://hydracards.hydracad.com/cards/card-564

 

Solution:

The calculation process must be completed successfully before a final printout is created.


2.
Cause:

A series of unfortunate events;

1. Dual city calculation where two calcs are generated by to two 'city' sources.  For example, the secondary calculation adds 333 gpm to the system.  It will be "added" to the primary calcuation as +-333 in the FLOW column.

 

2. Pump is involved

 

3. The secondary city flow is added between the pump and the primary city source, not between the pump and the demand area.

Solution:

Unsure if there's a solution.  The program will not accept a reverse hose demand (added flow) between the pump and the source.

Updated: Sept. 17, 2022, 9:49 p.m. Created: Oct. 26, 2020, 9:09 p.m.