AutoCAD Based HydraCALC (Ribbon/Toolbar/Location)

Button: Calculate

Description:

All data was lost in a calculation. Calc file is empty when opened. All Data Lost HydraCALC

Solutions:

Cause:

When attempting to run a calculation with a pump + city water supply, a reference point which did not exist in the 'System Piping' tab was used as the 'Remote Point' in the Pre-Calc Setup window. The resulting error 'The specified remote node does not have a k-factor. Please fix your input' then triggers a run-time error 5 which then wipes out the data.

Solution:

The user must NOT save the data when exiting, otherwise the calc will be saved with no data. This is to be fixed in update 50.3.47