AutoCAD Based Calculations (Ribbon/Toolbar/Location)
Description:
"Hydraulic Engine not responding" and then an "Error 62 input past end of file" usually happens on 2nd area run through
Causes:
1. Missing elevation on a pipe not attached to system see example at bottom of this window.
2. Duplicate Hyd node on drawing i.e. - underground pipe that jumps to the building but there is no elevation defline on the underground pipe
Solutions:
1. Put an elevation on the pipe that is jumping. **this should be marked with an error circle when raising to the model mode**
2. Send drawing to Hydratec. Files to help track down the issue are located in "HES\TEMP" V50CalcTemp_Backup.tmp and HACErrorLog.txt files