Revit Based HydraCAD (Ribbon/Toolbar/Location)
Description:
No error, but the rounding of the loose fitting and coupling schedule's rounding is behaving incorrectly to what's desired, for example, rounding 1-1/2” to 2”.
The rounding setting of the schedule is set to the nearest inch, and is reporting 1-1/2" inch as 2".
In sprinkler piping, measurements like 1/2", 3/4", 1", 1-1/4", 1-1/2", etc. are frequently used, so rounding to the nearest inch is losing these measurements.
Go to... The Manage Ribbon > Under the Settings panel, Select Project Units > Piping > Pipe Size > Rounding and change the rounding in the drop-down menu to be 1/4" or more accurate.