Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

Revit Based HydraCAD (Ribbon/Toolbar/Location)

Error Type: None

Description:

No error, but the rounding of the loose fitting and coupling schedule's rounding is behaving incorrectly to what's desired, for example, rounding 1-1/2” to 2”.

Solutions:

Cause:

The rounding setting of the schedule is set to the nearest inch, and is reporting 1-1/2" inch as 2".

In sprinkler piping, measurements like 1/2", 3/4", 1", 1-1/4", 1-1/2", etc. are frequently used, so rounding to the nearest inch is losing these measurements. 

Solution:

Go to... The Manage Ribbon > Under the Settings panel, Select Project Units > Piping > Pipe Size > Rounding and change the rounding in the drop-down menu to be 1/4" or more accurate. 

Updated: Oct. 27, 2023, 1:13 p.m. Created: Oct. 23, 2023, 1:45 p.m.