Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

Revit Based HydraCAD (Ribbon/Toolbar/Location)

Button: Sleeves

Description:

No error, but when selecting the Sleeves button, the loading circle / hourglass will appear then disappear. But nothing will happen, the sleeves dialog box never comes up. 

Solutions:

Cause:

The SleeveData.txt file located at: Install location (Typically C:)\HES\Temp is corrupted or malfunctioning in some way, and needs to be deleted and replaced. 

Solution:

Navigate to the previously specified location, in this instance C:\HES\Temp and find the SleeveData.txt file and delete it. 

When running the sleeves command again, it will remake this file and it should go back to functioning properly. 

HOWEVER, after doing this fix the default values loaded into sleeves will be erased, so you'll have to enter values for Minimum Sleeve DiameterDefault Sleeve Length, and Clearance again. 

Updated: Sept. 19, 2022, 2 p.m. Created: March 14, 2022, 1:11 a.m.