Revit Based HydraCAD (Ribbon/Toolbar/Location)

Button: Couplings Function: Add Couplings Error Type: None

Description:

Couplings get closer than expected to outlets when cutting in. 

Solutions:

Cause:

Coupling's Maximum Distance from Existing Fittings setting is using the number entered as inches instead of feet. 

Solution:

Make sure you are on the latest version of the software (22.0.009 or later), and be sure to reenter your spacing as a length in Feet' - Inches", a typical spacing being 0' - 6", the minimum recommended length being 0' - 2", and the maximum being 1' - 0"

Updated: Sept. 20, 2022, 3:39 a.m. Created: Jan. 26, 2022, 7:51 p.m.