Description:
After calculating the system, the results show, "Your System Has a Deficit"
System is -nan(ind) psi over the Water Supply Curve
The end user somehow got a negative sign into the Fittings column
Don't put negative fittings in the Ftgs column
Pump data was zeroed out. Clicking MAKE NFPA CURVE doesn't correct the issue
You must return to the previous screen and delete the pump entry, then re-create a new pump
Missing water supply information
It's possible the -nan(ind) is legit if a demand calc is being run.
Verify you have a legitimate water supply in the calculation
There are pipes with zero length.
Correct input so all pipes have a positive length.