AutoCAD Based Sprinklers (Ribbon/Toolbar/Location)

Button: FSC Setup Error Type: Unhandled Exception

Description:

When trying to open the dialogue box to define a Flexible Sprinkler connection, the following message box error appears. 

Could not find file; FSC-INSERTDEFLINE.txt

Resolved in: 56.3.1909

Solutions:

Cause:

Caused by bug in program that created a corrupt text file for the dialog selections.

Solution:

Go to this folder; 

*InstallDrive:\HES\HydraCAD\Ver50\Programs\FTG\Flexible Sprinkler Connections\

Find and delete this file FSC-Selections.txt 

 

*-InstallDrive should be the drive letter that your Hydratec Software was installed on, should include the 'HES' folder.

 