AutoCAD Based HydraCALC (Ribbon/Toolbar/Location)

Button: Calculate Error Type: Runtime Error

Description:

Input past end of file Runtime error 62

Solutions:

Cause:

1. Pumps in series where they are input into water supplies in the wrong order. Safety margin at pump can not be calculated.

Solution:

1. Rearrange the water supplies order: Supply 1 is City Water Supply 2 is the 1st pump closest to the city water supply Supply 3 is the 2nd pump closest to the remote area.

Updated: Sept. 26, 2022, 11:16 a.m. Created: March 1, 2019, midnight