Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

Standalone HydraCALC (Location)

Button: Calculate Error Type: Runtime Error

Description:

Type Mismatch Runtime 13

 

Run-time Error 13

 

Solutions:


1.
Cause:

Flexible sprinkler connections with blank data values.

Solution:

Check the FSC fitting being used (ie. Fva) then go to Utilities|Alter Fittings and find the Fva fitting.  Click the X under 1" and make sure most if not all values are filled in.  If a 4Fva is being used in the calc, make sure up to 4 columns are filled in..


2.
Cause:

Some system fail with this error when calculating with city and pump - has something to do with Miscfunc. Can also be caused by lower case fitting short names

 

Solution:

If job works on your machine, send them a new copy of MiscFunc from your machine, if not pass to Steve because both MiscFunc programs may need to be replaced. Fix fitting short names

Updated: Sept. 14, 2022, 3:01 a.m. Created: March 1, 2019, midnight