AutoCAD Based HydraCALC (Ribbon/Toolbar/Location)

Button: Input

Description:

the equivalent k-factor specified for node _ is not an end point in the equivalent k section of the input. Please modify your input Input Error Hydracalc v50

Solutions:

Cause:

1. Bug in the information sheet. An @ symbol was used to start a row of input/text in the information sheet. 2. Equivalent K reference point had a leading space

Solution:

1. Review the data in the information sheet and remove any @ symbols which start a line of text. The @ symbol can occur within text, just not at the start of text. 2. Review reference points used in Equivalent K tab and fix. If problem cannot be found, enter NEW points to verify no leading spaces were used. GAB 2/03/16