Standalone HydraCALC (Location)

Button: Print Final Error Type: Runtime Error

Description:

Invalid procedure call or argument Run-time Error 5

Solutions:

Cause:

1. The number zero was input in the fittings column (instead of the letter O)

2. With fixed flows only, flows defined as an "H' will cause this error.

3. Pipe length entered with an inch mark, such as 8"

4. Standpipe calculation put in with all H's instead of +

5. File saved as a .wef instead of a .wxf

6. System.ini empty

7. Dead end pipe in input.

Solution:

1. Change input so it is not "0" but "O"

2. Change input, the 1st fixed flow should be a "+", not an "H"

3. change pipe length to a decimal

4. Make ALL standpipe flows + NOT H unless it's actually hose in the underground.

5. Correct file extension

6. Find a copy of "C:\HES\Common\Ver50\SYSTEM.INI" from a working computer and copy over.

7. Double check the intermediate printout for sprinklers with 0 flow/0 pressure to figure out where the dead end is. (GAB 1/26/16)