AutoCAD Based Calculations (Ribbon/Toolbar/Location)

Button: Start Autocalcs Function: Calc Area # Error Type: Runtime Error

Description:

Runtime Error 5 1.A.1

Resolved in: 55

Solutions:

Cause:

Causes:

1. Happens the first time when switching between an Imperial and a Metric calc, or vice-versa. User has not pushed the Sizing button

2. User has no caps on drawing, which makes it hard for AutoCalc to find its way through the piping

3. User had a number in the 3/4 spot in the tree schedule

4. Supply point is not on a deadend pipe

Solution:

Solutions:

1. Pick the sizing button just once when using a 'new' unit system (not needed again unless switching unit systems again)

2. Add some caps (fixed in current version)

3. Put number in 1" instead of 3/4"

4. Place supply point on a deadend pipe.

Updated: Sept. 18, 2023, 2 p.m. Created: March 1, 2019, midnight