Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

Revit Based HydraCALC (Ribbon/Toolbar/Location)

Button: Hydraulic Calculations Function: Continue Error Type: Runtime Error

Description:

Step 1a.3 - Attaching Fittings - Fitting is a... Then Runtime Error 5 Invalid Procedure Call or Argument

Solutions:


1.
Cause:

Two fittings end to end with no pipe in between, such as a tee with a reducing coupling on top, then sprinkler head.

Solution:

Move fittings apart and add a pipe between them, or eliminate the reducing coupling, edit the tee to be a reducing tee, move sprinkler into tee. Does not happen in ver 5.0.


2.
Cause:

A device was added but was not uppercase.

Solution:

Make the device letter uppercase.

Updated: April 1, 2024, 1:32 p.m. Created: June 30, 2016, midnight