AutoCAD Based HydraCAD Residential (Ribbon/Toolbar/Location)

Button: Perform Hydraulic Calculations Error Type: Runtime Error

Description:

Collecting Special Fitting Information runtime error 9: subscript out of range Runtime Error 9,

Solutions:

Cause:

1. line is broken and tee inserted where there should not be a tee. In this case a sprinkler was close enough to the line to break the line but not connect to it. 2. floor to floor connection inserted directly on a sprinkler

Solution:

1. erase the fitting and move the sprinkler to the line, or erase the fitting and redraw the line. 2. move the floor to floor connection off of the sprinkler.

Updated: Sept. 19, 2022, 6:27 p.m. Created: March 1, 2019, midnight