AutoCAD Based 3D Modeling (Ribbon/Toolbar/Location)

Button: Show System Model

Description:

Sprinkler heads not defined in the drawing or no 3D block assigned for a sprinkler head. Going to Navis only - corrupt Persistent Model drawing? eKeyNotFound Dialog box HydraCAD

Solutions:

Cause:

Sprinkler heads not defined in the drawing or no 3D block assigned for a sprinkler head. Going to Navis only - corrupt Persistent Model drawing?

Solution:

1. Run checkups before raising to 3D (LCH command)

2. Rebuild HydraCAD layers (RBL command)

3. Make sure sprinkler heads are defined (eg. blue boxes in ACC1 layer)

4 If the user is using plugs, no 3D block has been assigned to its blue box in ACC1. Edit the BLKRDEF1 block for the plug by adding a value to the 3D_HEAD_BLOCK line. Use 3dHSW, 3dPEN or 3dUPR to represent a sidewall, pendent or upright respectively.

5. Delete the Persistent Model drawing, then reexport to Navis. GAB 9/30/14 GAB 11/08/15 JB 12/4/15