Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

AutoCAD Based Calculations (Ribbon/Toolbar/Location)

Button: Start Autocalcs

Description:

When starting the AutoCALC process, you get the error Unhandled exception has occurred in a component of your application

Key cannot be null

Parameter name: key.

Expanding DETAILS shows this information;

Application does not support just-in-time (JIT)
debugging. See the end of this message for details.

************** Exception Text **************
System.ArgumentNullException: Key cannot be null.
Parameter name: key
   at System.Collections.Hashtable.Insert(Object key, Object nvalue, Boolean add)
   at HCAD_HUI_CALC.CalcClass_Utilities.GetNodesOfPipesThatAreVertical(String FitID, Calc_File myCalcFile)
   at CalcingNameSpace.AutoCalcForm.MakeCalcFiledataPart1(Database db, Calc_File& MyCalcFile)
   at CalcingNameSpace.AutoCalcForm.SetupCalcFile()

Solutions:

Cause:

Reference points were added to top/middle/bottom of a stacked riser nipple, however those points were not part of the path where water is flowing through.

Solution:

Temporarily remove those reference points. [GAB 4/11/16]

Updated: Sept. 18, 2023, 12:47 p.m. Created: March 1, 2019, midnight