Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

AutoCAD Based Sprinklers (Ribbon/Toolbar/Location)

Button: FSC Insert Error Type: None

Description:

No error reported for FSC even when maximum length is clearly exceeded

 

If you view the FSC properties, it's possible the HoseLength and MaxNumberOfBends values are not set.

Solutions:

Cause:

OverPercent and UnderPercent in dialog properties are not set or incorrectly set or have bad data (non numeric values)

Solution:

1. Set values in the two text boxes on the dialog PROPERTIES tab in the Flexible Sprinkler Dialog box.

 

2. Delete the current FSC definition block (do NOT try to salvage/fix it)

 

3. Create a new FSC definition

- thanks Anthony S

Updated: June 14, 2024, 2:46 p.m. Created: Dec. 1, 2022, 12:04 p.m.