Hydratec Inc.

Need to save a card for later?

Create a bookmark folder in your browser of choice (Chrome, Firefox...), and save individual cards in your bookmarks to view here later.

AutoCAD Based HydraCAD Residential (Ribbon/Toolbar/Location)

Button: Perform Hydraulic Calculations Error Type: Runtime Error

Description:

run-time error '-2145386476 (80200014) key not found Run-Time Error ...,

Solutions:

Cause:

1. line type dot2 is missing from the drawing 2. 2 head calculation connection line does not connect to 2 sprinklers

Solution:

1. manually load the linetype go to - Linetype.... pick Load.... pick DOT2 from the list of linetypes. run the calculations again, after another error, if you sort by linetype DOT2, you will find the the 2 head connection that isn't connected 2. carefully look at all 2 head connection lines and find the one (or ones), that are not connected.

Updated: Sept. 14, 2022, 3:02 a.m. Created: March 1, 2019, midnight